Audi Q7: Vehicles with Restrictor, Receiver/Dryer and A/C Compressor Regulator Valve
-N280-, Checking Pressures, Externally Regulated Compressor
General Information
Note
- Connect the Air Conditioning (A/C) service station. Refer to
→ Chapter "A/C Service Station, Connecting".
- Observe the test requirements. Refer to
→ Chapter "Pressures, Checking".
- If a malfunction occurs at only one evaporator in vehicles
with two evaporators, also check pressures in the refrigerant
circuit, are these OK? Check the line connection between the
evaporator in question and the exit of line connection at
distribution point of refrigerant lines (for constriction). If
no malfunction can be detected, discharge the refrigerant
circuit and charge it with the specified refrigerant quantity.
Then check pressures and cooling performance of A/C system
again; if the malfunction occurs again, replace the expansion
valve which is prematurely switched by the malfunctioning
evaporator. Refer to
→ Heating, Ventilation and Air Conditioning; Rep. Gr.87; System
Overview - Refrigerant Circuit (vehicle-specific
repair manual).
- With the ignition switched off, check the pressure in the
refrigerant circuit (using the service station). Refer to
→ Chapter "Refrigerant Circuit, Checking Pressure with Service
Station".
The pressures with the ignition turned off meet the
specifications.
- Start the engine.
- Bring the engine speed up to 2000 RPM.
- Observe the pressure gauge of the service station.
Note
- Switching pressures for actuation of A/C Compressor
Regulator Valve -N280- and Radiator Fan -V7- are
vehicle-specific.
- Pressures must be measured at service connections; component
locations of these connections are vehicle-specific. Refer to
→ Heating, Ventilation and Air Conditioning; Rep. Gr.87; System
Overview - Refrigerant Circuit (vehicle-specific
repair manual).
Specified Values for Refrigerant Circuit Pressures
High-Pressure Side:
Increasing from initial pressure (when connecting the
pressure gauges) to a maximum of 20 bar (290 psi).
Low Pressure:
Decreasing from initial pressure (when connecting pressure
gauges) to the value in the graph.
A - Low pressure (measured at service connection) in bar (psi)
B - Control current for A/C Compressor Regulator Valve -N280- in
amps.
C - Permissible tolerance range (applicable to compressor
capacity utilization of 10 to 90%)
Note
- If high cooling output is needed (for example, the outside
temperature is very high, the blower speed it set on high but
the engine RPMs are low), then the A/C compressor will not bring
the pressure on the low pressure side to the value specified in
the diagram -C- (for example, for a
certain time after turning on the A/C). The A/C compressor is
actuated with maximum specified control current, however
delivery volume is no longer sufficient at this engine speed to
reduce pressure on low-pressure side to value in graph. To check
the A/C compressor control under these conditions, for example,
the fresh air blower is controlled only with approximately 40%
of the maximum voltage, check the pressures at a lower fresh air
blower speed. Use the Vehicle Diagnostic Tester ("OBD" or
"Guided Fault Finding for the A/C system") and
→ Heating, Ventilation and Air Conditioning; Rep. Gr.00; Repair
Instructions; Checking Cooling Output or
→Heating, Ventilation and Air Conditioning; Rep. Gr.87
(vehicle-specific repair manual).
- Under unfavorable conditions (very high ambient
temperatures, high humidity), pressure on high-pressure side may
increase to max. 29 bar (421 psi).
- Control current -B- is
displayed in measured value block of A/C Control Head -E87- or
control head, Climatronic Control Module -J255-.
- The high pressure measured from the High Pressure Sensor
-G65- (or the A/C Pressure/Temperature Sensor -G395- or the
Refrigerant Circuit Pressure Sensor - G805-) is displayed as the
measured value (from the Front A/C Display Control Head -E87-,
the A/C Control Module -J301- or the display and control unit,
and the A/C Control Module -J255-).
- Low pressure settles depending on control current for A/C
Compressor Regulator Valve -N280- and control characteristic of
expansion valve within compressor output range in tolerance
range.
- Under unfavorable conditions (very high ambient
temperatures, high humidity), compressor output may not always
be sufficient to attain the specified value.
- If compressor capacity utilization is greater than 90%,
pressure on low-pressure side may be in excess of tolerance
range "C" shown in graph (compressor output no longer
sufficient).
- The specified operating current for the A/C Compressor
Regulator Valve -N280- must be greater than 0.3 A in order to
ensure reliable regulator valve actuation.
- In "maximum cooling output" setting, control current for A/C
Compressor Regulator Valve -N280- is regulated to approximately
0.65 A (up to 0.85 A). This measured value is vehicle-specific
and displayed in the measured value block.
- At absolute pressure, 0 bar/psi corresponds to absolute
vacuum. Normal ambient pressure corresponds to 1 bar (14.5 psi)
absolute pressure. On the scales of most pressure gauges, 0 bar/psi
corresponds to an absolute pressure of 1 bar (14.5 psi) (can be
seen from -1 bar (-14.5 psi) mark below 0). Use the Vehicle
Diagnostic Tester ("OBD" or "Guided Fault Finding for the A/C
System") and
→ Heating, Ventilation and Air Conditioning; Rep. Gr.00; Repair
Instructions; Checking Cooling Output or
→Heating, Ventilation and Air Conditioning; Rep. Gr.87
(vehicle-specific repair manual).
Note
- If no fault is found with this malfunction, clean the refrigerant
circuit (flush using refrigerant R134a. Refer to
→ Chapter "Refrigerant Circuit, Cleaning (Flushing), with Refrigerant
R134a"; or blow through using compressed air and nitrogen.
Refer to
→ Chapter "Refrigerant Circuit, Flushing with Compressed Air and
Nitrogen".
- Check the measured values from the Evaporator Vent Temperature
Sensor -G263- and the -N280- control. If measured value of Evaporator
Vent Temperature Sensor -G263- is not OK, evaporator may ice up or
cooling output is not attained.
- If air conditioner operation is not OK when test is repeated after
replacing expansion valve, install old expansion valve, clean
refrigerant circuit (flush using refrigerant R134a. Refer to
→ Chapter "Refrigerant Circuit, Cleaning (Flushing), with Refrigerant
R134a"; or blow through using compressed air and nitrogen.
Refer to
→ Chapter "Refrigerant Circuit, Flushing with Compressed Air and
Nitrogen". Then replace the A/C compressor and
receiver/dryer.
- With this malfunction, evaporator may ice up although the quantity
of refrigerant in circuit is OK.
- If the expansion valve is malfunctioning (permanently closed or does
not open sufficiently), the A/C A/C Compressor Regulator Valve -N280- is
actuated to maximum output and low pressure drops to value in graph or
below (compressor draws off refrigerant from low-pressure side). Since
refrigerant cannot flow via expansion valve, cooling output is not
attained, high pressure may also not increase or only increase slightly
due to the absence of energy Vehicle Diagnostic Tester ("OBD" or "Guided
Fault Finding for the A/C System") and
→ Heating, Ventilation and Air Conditioning; Rep. Gr.00; Repair
Instructions; Checking Cooling Output or
→Heating, Ventilation and Air Conditioning; Rep. Gr.87
(vehicle-specific repair manual).
Note
- Make sure the A/C compressor (the A/C compressor shaft) is
actually being driven by the belt pulley/drive unit
→ Heating, Ventilation and Air Conditioning; Rep. Gr.87; A/C
Compressor (vehicle-specific repair manual).
- As of MY 2012, certain engines and A/C compressors that in
addition to the A/C A/C Compressor Regulator Valve -N280-, have
an A/C clutch -N25- attached to the belt pulley. Make sure the
A/C A/C Compressor Regulator Valve -N25- is indeed being
actuated and the A/C compressor (A/C compressor shaft) is being
driven by the belt pulley. Refer to
→ Heating, Ventilation and Air Conditioning; Rep. Gr.87; A/C
Compressor (vehicle-specific repair manual) and to
the Parts Catalog.
Note
- If the function of the A/C system is not OK when the test is
repeated, replace the expansion valve and receiver/dryer.
- With this malfunction, evaporator may ice up although the quantity
of refrigerant in circuit is OK.
- If expansion valve is malfunctioning (permanently closed or does not
open sufficiently), AA/C Compressor Regulator Valve -N280- is actuated
to maximum output and low pressure drops to value in graph or below
(compressor draws off refrigerant from low-pressure side). Since
refrigerant cannot flow via expansion valve, cooling output is not
attained, high pressure may also not increase or only increase slightly
due to the absence of energy. Use the Vehicle Diagnostic Tester ("OBD"
or "Guided Fault Finding for the A/C System") and
→ Heating, Ventilation and Air Conditioning; Rep. Gr.00; Repair
Instructions; Checking Cooling Output or
→Heating, Ventilation and Air Conditioning; Rep. Gr.87
(vehicle-specific repair manual).
- If there is too much refrigerant oil in the circuit, the compressor
must be drained and the receiver/dryer must be replaced. After cleaning
the refrigerant circuit (flushing with refrigerant R134a. Refer to
→ Chapter "Refrigerant Circuit, Cleaning (Flushing), with Refrigerant
R134a"; or blowing through using compressed air and nitrogen.
Refer to
→ Chapter "Refrigerant Circuit, Flushing with Compressed Air and
Nitrogen"), the correct quantity of refrigerant oil is filled
into the circuit. Refer to
→ Chapter "Approved Refrigerant Oils and Capacities".
Note
- It is not initially necessary to clean the refrigerant circuit
(flush using refrigerant R134a. Refer to
→ Chapter "Refrigerant Circuit, Cleaning (Flushing), with Refrigerant
R134a" or blow through using compressed air and nitrogen.
Refer to
→ Chapter "Refrigerant Circuit, Flushing with Compressed Air and
Nitrogen" when this problem occurs since normally there is
only a small quantity of moisture in the system which can be removed by
lengthy evacuation.
- If a problem involving moisture in refrigerant circuit only occurs
after a lengthy operating period or only infrequently (low pressure
drops below specification and evaporator ices up), it is sufficient to
replace the dryer installed in receiver/dryer (adjust quantity of
refrigerant oil). Refrigerant circuit is then to be evacuated for at
least three hours.
- With this malfunction, evaporator may ice up although the quantity
of refrigerant in circuit is OK.
- Problem with Evaporator Vent Temperature Sensor -G263- can also
cause icing-up of refrigerant circuit. If this problem is encountered,
also pay attention to measured value of Evaporator Vent Temperature
Sensor -G263-. Use the Vehicle Diagnostic Tester ("OBD" or "Guided Fault
Finding" for the A/C System) and
→ Heating, Ventilation and Air Conditioning; Rep. Gr.00; Repair
Instructions; Checking Cooling Output or
→Heating, Ventilation and Air Conditioning; Rep. Gr.87
(vehicle-specific repair manual).
Note
- For the malfunction "high pressure normal, low pressure too low",
note the following: With this malfunction, evaporator may ice up
although the quantity of refrigerant in circuit is OK.
- If the problem is with the -N280- A/C A/C Compressor Regulator Valve
(regulator valve is not actuated but A/C compressor operates
nevertheless), refrigerant circuit does not have to be cleaned (flush
with refrigerant R134a. Refer to
→ Chapter "Refrigerant Circuit, Cleaning (Flushing), with Refrigerant
R134a"; or blow through using compressed air and nitrogen.
Refer to
→ Chapter "Refrigerant Circuit, Flushing with Compressed Air and
Nitrogen"). In this case, it is sufficient to replace the A/C
compressor (observe quantity of refrigerant oil in A/C compressor).
- If the expansion valve is malfunctioning (permanently closed or does
not open sufficiently), the A/C A/C Compressor Regulator Valve -N280- is
actuated to maximum output and low pressure drops to value in graph or
below (compressor draws off refrigerant from low-pressure side). As
however refrigerant cannot flow via the expansion valve, the cooling
output is not attained and high pressure may also not increase or only
increase slightly due to the absence of energy conversion.
- Check the measured values from the Evaporator Vent Temperature
Sensor -G263- and the -N280- control. If the measured value from the
Evaporator Vent Temperature Sensor -G263- is incorrect, the evaporator
may ice up or cooling output is not attained. Use the Vehicle Diagnostic
Tester ("OBD" or "Guided Fault Finding for the A/C System") and
→ Heating, Ventilation and Air Conditioning; Rep. Gr.00; Repair
Instructions; Checking Cooling Output or
→Heating, Ventilation and Air Conditioning; Rep. Gr.87
(vehicle-specific repair manual).
Note
- This fault may also be caused by too much refrigerant oil in the
circuit. Overfilling with refrigerant oil can occur if, for example, the
compressor has been replaced without adjusting the quantity of
refrigerant oil.
- If the expansion valve is malfunctioning (permanently closed or does
not open sufficiently), the A/C A/C Compressor Regulator Valve -N280- is
actuated to maximum output and low pressure drops to value in graph or
below (compressor draws off refrigerant from low-pressure side). Since
refrigerant cannot flow via expansion valve, cooling output is not
attained, high pressure may also not increase or only increase slightly
due to the absence of energy. Use the Vehicle Diagnostic Tester ("OBD"
or "Guided Fault Finding for the A/C System") and
→ Heating, Ventilation and Air Conditioning; Rep. Gr.00; Repair
Instructions; Checking Cooling Output or
→Heating, Ventilation and Air Conditioning; Rep. Gr.87
(vehicle-specific repair manual).
Note
- Overfilling with refrigerant oil can occur if, for example, the
compressor has been replaced without adjusting the quantity of
refrigerant oil.
- If expansion valve is malfunctioning (permanently open), evaporator
temperature is no longer regulated such that only refrigerant in gaseous
state exits from the evaporator. Under certain usage conditions, liquid
droplets may then be drawn in by the compressor and cause noise (liquid
cannot be compressed).
- If there is too much refrigerant oil in the circuit, the compressor
must be drained and the receiver/dryer must be replaced. After cleaning
the refrigerant circuit (flushing with refrigerant R134a. Refer to
→ Chapter "Refrigerant Circuit, Cleaning (Flushing), with Refrigerant
R134a"; or blowing through using compressed air and nitrogen.
Refer to
→ Chapter "Refrigerant Circuit, Flushing with Compressed Air and
Nitrogen"), the correct quantity of refrigerant oil is filled
into the circuit. Refer to
→ Chapter "Approved Refrigerant Oils and Capacities".
READ NEXT:
General Information
Extremely Dangerous Due to High-Voltage
The high-voltage system is under high-voltage. Death or serious
bodily injury by electric shock.
- Individuals with electronic/medical
Note
On vehicles with a high-voltage system but without a heat
pump (for example on Audi A3 e-tron, Audi Q5 hybrid, Audi A6
hybrid and Audi A8 hybrid) no check valves are installed in the
r
Note
On vehicles with a high-voltage system and heat pump (for
example on the Audi Q7 e-tron) installed in the refrigerant
circuit and electrically activated vehicles which regulate the
f
SEE MORE:
Overview - Intake Manifold Lower Section with Fuel Rail
MPI Low Pressure Fuel Injection
Note
The components for cylinder bank 2 (left) are shown in the
illustration.
1 - Vacuum Hose
To the Intake Manifold Runner Control Valve -N316-
2 - O-Ring
Replace after removin
Overview - Emissions Control System
1 - Front Muffler
With the coupling, the coupling must not be bent more than 10º -
otherwise it may be damaged
Removing and installing. Refer to
→ Chapter "Front Muffler, Removing and Installing".
Exhaust System, Installing without Tension